Each water softener system shall be capable of handling and treating without long term deleterious effect on resin life, on raw water with the following characteristics ;
  • Turbidity (Silica Scale) : Max 5
  • Colour (Hazen units) : Max 10
  • Iron (Fe) (soluble) : Max 0.5 ppm
  • Manganese : Max 0.5 ppm
  • Copper (Cu) : Max 0.3 ppm
  • Total solids : Max 100 ppm
  • Suspended solids : Max 10 ppm
  • Total Hardness (CaCo3) : Max 20 ppm
  • Chlorides (Cl) : Max 30 ppm
  • Nitrates (NO3) : Max 0.5 ppm
  • Oxygen content : Max 2.0 ml/litre
  • pH value : 5 - 9

Source : Tender Specifications / BEA